Original graphic from AESO

The Alberta Electric System Operator (AESO) declared its third grid alert in three days as frigid temperatures continued to blanket the province on Jan. 14, driving up electrical demand while reducing available renewable power supply.

The “grid alert” was declared at 3:42 p.m. and posted to X at 3:52 p.m. Temperatures across Alberta ranged from -40 in the north at High Level, to -32 C in Edmonton, -29 C in Calgary and -29 C in Lethbridge. That’s a critical point, because around -30 C, wind generation is usually shut down to prevent cold brittle behaviour of materials causing catastrophic failures of wind turbines. Usually, but as the day would go on, prove to be not always.

But even so, the temperature wouldn’t matter so much since there was next to no wind in southern Alberta, where the 45 wind farms are located. There was only 3 knots of wind at Lethbridge and Pincher Creek, 4 knots at Vulcan and Medicine Hat, according to Windy.com at the time of the alert.

According to X bot account @ReliableAB, which posts hourly updates of AESO data on the Alberta grid, At 3:39 p.m., solar was falling, with 332 megawatts being produced from the 1,650 megawatts of grid-scale solar.

  • 0081 OSY 2024 hockey draft
    0081 OSY 2024 hockey draft
  • 0077 Caprice Resources Stand Up For Free Speech
    0077 Caprice Resources Stand Up For Free Speech
  • 0076 Latus only
    0076 Latus only
  • 0061 SIMSA 2024 For Sask Buy Sask
    0061 SIMSA 2024 For Sask Buy Sask
  • 0055 Smart Power Be Smart with your Power office
    0055 Smart Power Be Smart with your Power office
  • 0051 JML Hiring Pumpjack assembly
    0051 JML Hiring Pumpjack assembly
  • 0049 Scotsburn Dental soft guitar
    0049 Scotsburn Dental soft guitar
  • 0046 City of Estevan This is Estevan
    0046 City of Estevan This is Estevan
  • 0041 DEEP Since 2018 now we are going to build
    0041 DEEP Since 2018 now we are going to build
  • 0032 IWS Summer hiring rock trailer music
  • 0022 Grimes winter hiring
  • 0021 OSY Rentals S8 Promo
  • 0018 IWS Hiring Royal Summer
  • 0013 Panther Drilling PO ad 03 top drive rigs
  • 0011
  • 0006 JK Junior
  • 0002 gilliss casing services
    0002 gilliss casing services
  • 9002 Pipeline Online 30 sec EBEX
    9002 Pipeline Online 30 sec EBEX
  • 9001

 

Wind had been minimal since the previous night. Indeed, for several points the morning of Jan. 14, there was zero power produced at all from Alberta’s 45 wind farms, with a total installed capacity of 4,481 megawatts. And this corresponded with zero solar power at the same time, meaning the 6,131 megawatts of wind and solar were producing zero power. During the 8 a.m. hour, four of Alberta’s grid-scale batteries were called upon to provide power to the grid, according to Dispatcho.app, a website which logs the minute-by-minute data from the AESO. That was highly unusual, as the grid-scale batteries are rarely, if ever, deployed in the morning.

 

Earlier in the day, Alberta Premier Danielle Smith had warned of the possibility of another grid alert. At 11:28 a.m., she posted on X, “Thank you to everyone who quickly took action last night to reduce electricity use. Your action kept Albertans safe and warm and our grid functioning. Unfortunately, due to today’s continued extreme weather, we’re not out of the woods yet. To avoid another risk to our electricity grid, please continue to be diligent and avoid unnecessary electricity use. Turn off unnecessary indoor and outdoor lights and delay the use of major power-consuming appliances. Peak hours are between 4pm-8pm so it’s especially important to watch usage during this time.”

 

Earlier in the afternoon, Alberta was exporting power to both British Columbia and Montana. But by 4:08 p.m., it was importing 267 megawatts, including 89 from Saskatchewan.

Contingency reserve falls

By 4:37 p.m., AESO data showed the dispatched contingency reserve (DCR) had fallen substantially. All available 548 megawatts hydro was thrown into the grid, with none in reserve. All that was left in the the AESO’s reserve back pocket was 12 megawatts of natural gas and 115 megawatts of batteries, with 15 megawatts of batteries already in play producing power to the grid. But at full output, Alberta’s nine 20 megawatt batteries typically only produce that much power for an hour. And the last 20 megawatts of solar was about to disappear off the board, with only 103 megawatts of wind on the grid, out of the 4,481 megawatts of grid-scale wind installed.

Out of 87 natural gas-fired generating units (including one coal/gas dual fuel), only one unit has any additional capacity – Air Liquide Scotford No. 1, which had 12 megawatts of capacity for the DCR.

By 4:58, 262 megawatts of hydro were back on the contingency reserve board, with total DCR standing at 389 megawatts. That was odd, as the day before, total hydro net to grid plus DCR at 6:53 pm. was 323 megawatts. by at 5:05 p.m. on Jan. 14, the available hydro dramatically increased. In the space of 23 hours, somehow the total hydro capacity shot up to 677 megawatts, more than double what was available on Jan. 13.

  • 0081 OSY 2024 hockey draft
    0081 OSY 2024 hockey draft
  • 0077 Caprice Resources Stand Up For Free Speech
    0077 Caprice Resources Stand Up For Free Speech
  • 0076 Latus only
    0076 Latus only
  • 0061 SIMSA 2024 For Sask Buy Sask
    0061 SIMSA 2024 For Sask Buy Sask
  • 0055 Smart Power Be Smart with your Power office
    0055 Smart Power Be Smart with your Power office
  • 0051 JML Hiring Pumpjack assembly
    0051 JML Hiring Pumpjack assembly
  • 0049 Scotsburn Dental soft guitar
    0049 Scotsburn Dental soft guitar
  • 0046 City of Estevan This is Estevan
    0046 City of Estevan This is Estevan
  • 0041 DEEP Since 2018 now we are going to build
    0041 DEEP Since 2018 now we are going to build
  • 0032 IWS Summer hiring rock trailer music
  • 0022 Grimes winter hiring
  • 0021 OSY Rentals S8 Promo
  • 0018 IWS Hiring Royal Summer
  • 0013 Panther Drilling PO ad 03 top drive rigs
  • 0011
  • 0006 JK Junior
  • 0002 gilliss casing services
    0002 gilliss casing services
  • 9002 Pipeline Online 30 sec EBEX
    9002 Pipeline Online 30 sec EBEX
  • 9001

 

Contingency hits zero

At 5:08 p.m., Alberta’s contingency reserve fell to zero across the board, despite a required contingency of 500 megawatts. There was no additional hydro, gas or coal available. The six available batteries were all put into action, providing 79 megawatts between them for about 10 minutes.

At 5:08 p.m., Alberta’s electrical grid had nothing left in reserves. The column on the right is Dispatched (and accepted) Contingency Reserve was zeros across the board. AESO

That zero highlighted was supposed to be the 500 megawatts indicated above. Alberta had nothing in the tank at that point, at 5:08 pm. AESO

 

At 5:24, the AESO website started showing the batteries listed as both contributing power to the grid and being on the DCR list, which combined far exceeded their rated capacity. This was likely a reporting error, as eReserve6, for example, was showing contributing 15 megawatts while having a further 20 megawatts of dispatched contingency reserve, a total of 35 megawatts despite its 20 megawatt capacity. A few minutes later this glitch seemed to sort itself out and six batteries were once again on the DCR.

Around this time, imports jumped to 608 megawatts, with 434 coming from British Columbia, 21 from Montana, and 153 (the maximum possible) from Saskatchewan. Hydro now had 60 megawatts on the DCR list, but still no additional natural gas was available.

British Columbia to the rescue

As the 6 o’clock hour progressed, British Columbia substantially increased its power exports to Alberta. by 6:45, that number was 496 megawatts, while Montana was contributing 14 and Saskatchewan 153. The total 664 made a big impact on Alberta’s ability to put 253 megawatts of hydro onto its contingency board. By this point, there was now 92 megawatts of gas available, and the contingency reserve hovered around 432 megawatts – a much more comfortable margin than it had been an hour and a half before.

That was important, too, because by this point, only four of Alberta’s t0 grid-scale batteries had any juice left. While they had done their job several times in the past three days, filling in for short times when needed most, the fact that six of those batteries were no longer showing on the DCR list also revealed their limitations.

Wind had also built up to 215 megawatts. Despite -34 C conditions, the Halkirk Wind Power Facility, east of Stettler, was producing 60 megawatts, having slowly built up power generation since 11:30 a.m. While a handful of the wind farms were

The AESO pool price for power remained at the set maximum of $999.99 per megawatt-hour from 5 to 9 p.m.

However, later in the evening, power imports into Alberta fell tremendously, and the grid alert still had not been called off. By 9:19, British Columbia imports fell to next to nothing before starting to pick up again. Saskatchewan’s contribution fell to 92 megawatts. And by this point the generation contingency reserve was hovering once again just over 200 megawatts. At 9:22 there was zero natural gas DCR available, 148 megawatts of hydro, and 115 megawatts of batteries available.

At 10:12 p.m., the AESO declared the end of the grid alert. It had lasted for 6.5 hours. At this point, 15 wind farms were providing at least some power, totaling around 255 megawatts. Sharp Hills, Lafine, Halkirk Grizzly Bear Creek and Blackspring Ridge made up most of it, while 34 wind farms were producing zero power.

American grid under stress, too

On the same day, a milder form of grid alert was issued by the Southwest Power Pool (SPP). The SPP runs from the Canada/US border south of Estevan to the Texas Panhandle, and incorporates all or part of 14 states in the Great Plains.

At 11:50 a.m. central time, the SPP said, “SPP is issuing a Conservative Operations Advisory for its entire Balancing Authority effective 4 a.m. CT Sunday, Jan. 14 with an anticipated end of 9 p.m. CT Tuesday, Jan. 16.

“Conservative Operations Advisories do not require the public to conserve energy, but are issued to raise awareness of potential threats to reliability among entities responsible for operating transmission and generation facilities. Individuals should contact their local utility for details specific to their area.”

At 6 p.m. central time, the SPP was getting 42 per cent of its power from natural gas, 33 per cent from coal, and 15 per cent from wind. On a more typical day, wind can account for half or more of the power generated in the SPP.

At the far end of the SPP, Texas’s grid operator, ERCOT, issued a “conservation appeal” for the morning of Monday, Jan. 15. from 6 – 10 a.m. CT, stating, “Operating reserves are expected to be low tomorrow morning due to continued freezing temperatures, record-breaking demand, and unseasonably low wind. We request Texas businesses and residents conserve electricity use, if safe to do so.”

 

ERCOT’s power forecast for Jan. 15 showed a projected 2,748 megawatt shortfall for 8 a.m. on Monday, Jan. 15. ERCOT

 

 

  • 0081 OSY 2024 hockey draft
    0081 OSY 2024 hockey draft
  • 0077 Caprice Resources Stand Up For Free Speech
    0077 Caprice Resources Stand Up For Free Speech
  • 0076 Latus only
    0076 Latus only
  • 0061 SIMSA 2024 For Sask Buy Sask
    0061 SIMSA 2024 For Sask Buy Sask
  • 0055 Smart Power Be Smart with your Power office
    0055 Smart Power Be Smart with your Power office
  • 0051 JML Hiring Pumpjack assembly
    0051 JML Hiring Pumpjack assembly
  • 0049 Scotsburn Dental soft guitar
    0049 Scotsburn Dental soft guitar
  • 0046 City of Estevan This is Estevan
    0046 City of Estevan This is Estevan
  • 0041 DEEP Since 2018 now we are going to build
    0041 DEEP Since 2018 now we are going to build
  • 0032 IWS Summer hiring rock trailer music
  • 0022 Grimes winter hiring
  • 0021 OSY Rentals S8 Promo
  • 0018 IWS Hiring Royal Summer
  • 0013 Panther Drilling PO ad 03 top drive rigs
  • 0011
  • 0006 JK Junior
  • 0002 gilliss casing services
    0002 gilliss casing services
  • 9002 Pipeline Online 30 sec EBEX
    9002 Pipeline Online 30 sec EBEX
  • 9001

 

Alberta’s electrical grid stood at the brink of blackouts Jan. 13, before pulling back in the nick of time

Alberta goes under grid alert for just under 5 hours on Jan. 12

Most of Alberta’s wind fleet slowly shut down Thursday night, but not for lack of wind